Dry-Type Transformers

SC(B) Epoxy-Resin Dry-Type Transformer

Vacuum-cast epoxy dry transformer, 30–2500 kVA: flame-retardant and self-extinguishing, +40 % output under AF forced-air cooling, long-term service at Class F 155 °C or Class H 180 °C.

Factory-direct supply Worldwide delivery & export documentation 12-month warranty · extended options
  • Excellent electrical performance with low partial discharge
  • Strong lightning-impulse and short-circuit withstand
  • High overload capability — AF forced-air cooling lifts output by 40 %
  • Flame-retardant, self-extinguishing, maintenance-free, moisture- and damp-heat-proof for harsh environments
  • High thermal class: continuous safe duty at 155 °C (Class F) or 180 °C (Class H)
At a glance

Built to perform, year after year

10·10.5 kV / 0.4 kV
HV / LV voltage
±2×2.5 %·±5 % / Dyn11·Yyn0
Tap range / vector group
4.0 / 6.0–8.0 %
Short-circuit impedance
A closer look

Engineered around safety, efficiency and uptime

Overview

SC(B) dry-type transformers have their coils integrally vacuum-cast in epoxy resin. They serve power stations and plants, industry, urban high-rises and user distribution substations across supply and distribution systems.

Product features

Excellent electrical performance with low partial discharge
Strong lightning-impulse and short-circuit withstand
High overload capability — AF forced-air cooling lifts output by 40 %
Flame-retardant, self-extinguishing, maintenance-free, moisture- and damp-heat-proof for harsh environments
High thermal class: continuous safe duty at 155 °C (Class F) or 180 °C (Class H)

Designation

Three-phase · resin-moulded · foil-wound LV coil · loss-level code · rated capacity (kVA) · system voltage (kV)

Technical specifications

Full specifications

Common data
HV / LV voltage
10·10.5 kV / 0.4 kV
Tap range / vector group
±2×2.5 %·±5 % / Dyn11·Yyn0
Short-circuit impedance
4.0 / 6.0–8.0 %
Loss data — typical ratings (F / H class load loss, W)
30 kVA — no-load / load
130·105 / 640·685
100 kVA — no-load / load
320·270 / 1665·1780
315 kVA — no-load / load
665·570 / 3590·3850
630 kVA — no-load / load
885·750 / 5365·5760
1250 kVA — no-load / load
1420·1205 / 8720·9335
2500 kVA — no-load / load
2450·2080 / 15445·16605
Note
斜线前 F 级 / 后 H 级;全系 30–2500kVA