Vacuum Circuit Breakers

ZW32-12 Outdoor Pole-Mounted Vacuum Breaker

10 kV feeder workhorse for urban and rural grids: 20/25 kA breaking with 30 full-fault operations, 10,000-cycle mechanical life, optional built-in disconnector and CT, −45…+40 °C service.

Factory-direct supply Worldwide delivery & export documentation 12-month warranty · extended options
  • Vacuum breaker · outdoor · design serial No. · rated voltage (kV) · G with disconnector / blank without · spri
At a glance

Built to perform, year after year

12kV
Rated voltage
42 / 48kV
1 min PF withstand (ph & earth / break)
75 / 85kV
Lightning impulse (ph & earth / break)
630 / 1250A
Rated current
A closer look

Engineered around safety, efficiency and uptime

Overview

A three-phase AC 50 Hz outdoor HV switchgear composed of pole columns, spring operating mechanism, enclosure and control unit. Widely used on 10 kV urban and rural distribution feeders to switch load, short-circuit and overload currents and provide protection in similar duties.

Model designation

Vacuum breaker · outdoor · design serial No. · rated voltage (kV) · G with disconnector / blank without · spring mechanism · rated current (A) · rated short-circuit breaking current (kA)

Service conditions

Ambient −45 °C … +40 °C; altitude ≤ 2000 m
Pollution class IV; wind ≤ 35 m/s (≈ 700 Pa)
No fire, explosion, chemical corrosion or constant severe vibration (self-induced excluded); customisation negotiable beyond these limits

Technical specifications

Full specifications

Technical parameters
Rated voltage
12 kV
1 min PF withstand (ph & earth / break)
42 / 48 kV
Lightning impulse (ph & earth / break)
75 / 85 kV
Rated current
630 / 1250 A
Short-circuit breaking current / times
20·25 kA / 30 次
Making & peak withstand current
50 / 63 kA
Short-time withstand / duration
20·25 kA / 4 s
Operating sequence
分-0.3s-合分-180s-合分
Mechanical life / operating voltage
10000 次 · AC/DC 220/110 V
Contact wear allowance / phase spacing
3 mm / 340 mm

Specifications are representative and may vary by configuration and region. Final figures are confirmed on the project datasheet.

Ready to power your next project?

Tell us about your load profile and site conditions — our engineers will help you size the right HiStore configuration.